ASCON Service Guide Book Diagnosis
56
Ceiling Cassette A/C Series Inverter-X Model
Model Board Handset
ACKX 20/25A/AR VA3.0 G18 / SLM3
ACKX 10/15/20C/CR VA3.0 G18 / SLM3
POWER
(Green)
TIMER
(Orange)
SLEEP
(Red)
HEAT
(Red)
Error
Code
(SLM3)
Operation / Faulty
Indication
Action
- Cooling mode -
- Timer On -
- Sleep mode On -
- Heating mode -
- Defrost mode -
E1
Indoor temperature
sensor loose / short
Check indoor coil sensor
connection / change indoor
coil sensor
E2
Outdoor temperature
sensor loose / short
Check outdoor coil sensor
connection / change
outdoor coil sensor
E3 Communication error
Check connection wires
between indoor and
outdoor
E4
Compressor overload
protection
If running ampere highly
increase, change the
compressor
E5 Pump fault
Clear the clogging at drain
pipe. If pump is not
working, change the pump
E6
Compressor overheat /
gas leak
Check for leakage & repair
/ Top up refrigerant
E7
IPM / PFC / Partial
switching
Check supply voltage and
compressor phase
E8 Outdoor over current
Check the input current
and discharge pressure
/