Acson ACM20ER Especificaciones Pagina 113

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 125
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 112
Diagnostic Guidelines
By means of pressure reading:
111
Pressure
Data
Circuit
Too low
A little low
Normal
A little high
Too high
Probable cause
High side
Low side
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
1. Poor compression / no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High side
Low side
1. Air intake temperature of indoor unit too high.
Downloaded from AC-Manual.com Manuals
Vista de pagina 112
1 2 ... 108 109 110 111 112 113 114 115 116 117 118 ... 124 125

Comentarios a estos manuales

Sin comentarios