5. SELECTION PROCESS
WATER PRESSURE DROP VS FLOW RATE
MODEL : A5ACV 30CR - COOLING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.26 109.00 26.56 82.44
1.30 108.40 26.59 81.81
1.32 108.20 28.94 79.26
1.36 108.00 31.54 76.46
1.39 107.20 31.39 75.81
1.43 106.00 31.81 74.19
1.49 105.00 32.30 72.70
MODEL : A5ACV 30CR - HEATING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.89 95.00 38.34 56.66
1.80 96.60 35.40 61.20
1.66 101.00 32.45 68.55
1.44 106.00 28.64 77.36
1.12 111.80 18.51 93.29
MODEL : A5ACV 55CR - COOLING
MODEL : A5ACV 55CR - HEATING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
2.82 175.47 66.10 109.37
2.79 179.25 68.52 110.73
2.73 182.26 67.30 114.96
2.44 200.00 67.98 132.02
1.89 226.42 67.92 158.50
50
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.58 240.00 69.64 170.36
1.97 222.64 67.41 155.23
2.28 207.55 67.18 140.37
2.52 194.34 66.91 127.43
2.68 185.28 67.64 117.64
2.78 180.00 68.11 111.89
2.80 176.98 66.33 110.65
Vista de pagina 51